A 100 W power supply can load the mains wiring like a 175 VA one. The ratio between the two is the power factor, and it is easy to measure wrongly: with two meters instead of a power analyzer, with cos φ instead of true PF, with an average-responding clamp meter, or over a scope window that is not a whole number of cycles. This guide shows engineers and technicians how to measure power factor correctly, including harmonics, THD and the IEC 61000-3-2 limits.
The illustrations in this guide are live: click the buttons under each one to change the load or the method and watch the numbers change.
1. What Is Power Factor?
PF = P / S with P = (1/T) ∫ v·i dt (W) and S = Vrms × Irms (VA)
Real power P is the average of the instantaneous product of voltage and current: the power that does work. Apparent power S is what the wiring, fuses, transformers and generators have to carry. A PF of 1 means every amp does useful work; a PF of 0.57 means the wiring carries 1.75 times the current a resistive load would need.
PF matters for wiring and breaker sizing, generator and UPS capacity, utility tariffs, and compliance: harmonic current limits (IEC 61000-3-2) and efficiency programs (for example, 80 PLUS certification requires a PF of at least 0.9 at full load).
2. Displacement vs Distortion
- Displacement: the current is a sine wave, but shifted in time from the voltage (motors, transformers, capacitor banks). Measured by cos φ of the fundamental.
- Distortion: the current is not a sine wave (capacitor-input rectifiers draw narrow peaks). Measured by the distortion factor DF = I1/Irms.
PF = cos φ × DF and, for a sinusoidal voltage, PF = cos φ / √(1 + THDi²)
3. Equipment You Need
| Item | Why |
|---|---|
| Power analyzer | Measures W, VA, PF, cos φ and harmonics with true-RMS inputs, wide bandwidth and high crest factor. A good DMM pair or a scope is not a substitute for compliance work. |
| Stiff, low-distortion AC source | Voltage distortion and source impedance change the current waveform and the PF. For harmonic testing, IEC 61000-3-2 sets requirements for the source voltage. |
| Current input or shunt | The analyzer’s direct current inputs, or a calibrated shunt or current sensor with enough bandwidth. Not an average-responding clamp meter. |
| Electronic load | To step the DUT through its load points. |
4. Power Analyzer Settings
| Setting | Use | Why |
|---|---|---|
| Synchronization | Voltage channel, line frequency | The analyzer must find the true cycle boundaries; syncing on peaky current can be unstable. |
| Averaging / update | Whole line cycles | Partial cycles bias P and the RMS values. |
| Current range | Crest factor ≥ 3 at your peak | Rectifier current has a crest factor around 3 or more; clipped peaks give wrong Irms and W. |
| Voltage range | Next range above the peak | Peak of 264 V AC is about 373 V. |
| Line filter / bandwidth | Off / wide for power and PF | A filter removes harmonic current and makes PF look better than it is. |
| Harmonic mode | Per IEC 61000-4-7 (10 cycles at 50 Hz, 12 at 60 Hz), up to the 40th | Required for IEC 61000-3-2 compliance results. |
| Wiring | Voltage at the DUT terminals | Avoids counting cable losses; use the analyzer’s wiring compensation if available. |
5. Test Conditions and the PF Curve
- Input voltage and frequency: 100/115/230/277 V as applicable, at 50 and 60 Hz.
- Load points: 10, 25, 50, 75, 100 %. Many specs quote PF at full load only, but PF usually falls at light load.
- Warm-up: until readings are stable.
- Plot PF vs load for each input voltage. With active PFC, PF is lowest at light load and high line, because the EMI-filter capacitor current becomes a large part of the small input current.
6. Harmonics, THD and IEC 61000-3-2
The current harmonics explain why the PF is low. Measure each odd harmonic up to the 40th, and the total harmonic distortion:
THDi = √(I2² + I3² + … + I40²) / I1
IEC 61000-3-2 limits harmonic currents of equipment up to 16 A per phase, in four classes:
| Class | Equipment | Limits |
|---|---|---|
| A | Balanced three-phase, household appliances, most others | Absolute values in A |
| B | Portable tools, non-professional arc welders | Class A × 1.5 |
| C | Lighting equipment | % of fundamental (with special rules for low power) |
| D | PCs, monitors, TVs from 75 W to 600 W | mA per watt, capped at Class A values |
7. Measurement Errors to Avoid
- Distorted source voltage: a flat-topped mains voltage changes the rectifier current and the PF. Use a clean source and record its THD.
- Source impedance: a weak source or long cables round off the current peaks and make PF look better.
- Low-bandwidth current sensors: a clamp with a few kHz of bandwidth loses the higher harmonics.
- Light load: currents are small; use the lowest current range that does not clip.
8. Step-by-Step Procedure and Report
- Connect the AC source → power analyzer → DUT → electronic load. Voltage sensed at the DUT terminals.
- Set sync to the voltage channel, whole-cycle averaging, voltage and current ranges with crest factor ≥ 3, line filter off.
- Set nominal input and full load; warm up until stable.
- Record Vrms, Irms, P, S, PF, cos φ, THDi and the source voltage THD.
- Repeat at each load point and each input voltage and frequency.
- In harmonic mode (IEC 61000-4-7), record the harmonic currents and compare with the applicable IEC 61000-3-2 class.
- Plot PF and THD vs load. Report the conditions, instrument and settings, and PASS/FAIL against your PF and harmonic requirements.
9. Common Mistakes and Fixes
| Mistake | Result | Fix |
|---|---|---|
| Reporting cos φ as PF | Looks near 1 for a rectifier | PF = W / VA |
| V × I from two meters | Only VA, no PF | Power analyzer for W |
| Average-responding meter | Wrong Irms, PF can exceed 1 | True-RMS analyzer inputs |
| Partial-cycle window | Biased, jumping readings | Sync, whole cycles |
| Current range clipped | Low Irms and W | Range with crest factor ≥ 3 |
| Line filter on | PF looks better than real | Filter off for power readings |
| Only full load tested | Light-load PF missed | Measure the PF curve |
| Distorted or weak source | Wrong PF and harmonics | Clean, stiff source; record its THD |
10. Power Factor Calculator
Calculate PF from your readings, split it into displacement and distortion, or list the Class D harmonic limits for your input power.